HVACLICENSE.COM
JUST FOR FUN TEST 5
* Required
The purpose of mechanical codes are to regulate the design, installation, maintenance, alteration, and inspection of mechanical systems that are permanently installed and utilized to provide control of environmental conditions and related processes within a building. Is this a True or False statement?
True
False
True and False
None of these
It shall be unlawful for a person, firm, or corporation to erect, construct, alter, repair, remove, install, demolish or utilize a mechanical system, or cause same to be done, in conflict with or in violation of any of the provisions of a mechanical code. Would this be a True of False Statement?
True
False
True and False
None of the above
An Approved Agency is?
Is established and recognized Agency
Approved by Code Officials
Regularly testing and furnishing inspection services
All of the above
What happens when requirements of your installation are not covered under a mechanical code, who is responsible, who do you ask?
Your Supervisor
Your Local Code Official
State Police
Local Police Department
When you see the term Shall in the code, what does this mean?
Maybe you need to do it
It must be done
Don't know
Review Twice
What does listed mean to you?
Licensed
Nationally recognized list of materials and equipment
Taking on water
None of the above
Energy utilization means what?
Equipment installed and designed for efficient utilization of energy
Gas, Oil and Electric Energy
Don't use Energy
Energy not wasted
Typically 1 cubic foot of natural gas is equal to how many Btuh?
1,000 Btuh
10,000 Btuh
100 Btuh
10 Btuh
Adequate room size is judged by determining if the room has sufficient volume as defined by the "1/20th" rule. The 1/20th rule states that if the volume, in cubic feet, of the Combustion Air Zone in which appliances are installed is less that 1/20th of the combined input rating of all appliances in Btu/hours, provisions shall be made to remedy the deficiency in combustion air. If there are no symptoms of insufficient air, the 1/20th rule does not apply. To find the the answer for the 1/20th rule you would?
Take the total room connected Btu/h appliance input rating and divide by 20
Take the total room connected Btu/h appliance input rating and multiply by 20
Take the total room connected Btu/h appliance input rating and subtract 20
Take the total room connected Btu/h appliance input rating and add 20
I would like to be a licensed professional for what reason?
Be more skilled
Be legal
Become more knowledgeable
All of the above
ENTER YOUR EMAIL FOR RESPONSE
*